Mains power supply | |
Voltage | 230/115 VAC, ±10%, 50/60 Hz |
Inrush current | 1.5 A @ 230 VAC / 3 A @ 115 VAC |
Max power consumption | 50 VA |
Idle / max load* current | 0.2 A / 0.3 A |
Battery power supply | |
Voltage | 24 VDC, +15% / -15% |
Current max | 1.8 A |
Typical / max load* current | 0.51 A / 1.5 A |
Trigger Inputs | 12 x (6 EMG, 6 business) |
Connectors | MC1,5 / 14-ST-3,5 |
Activation | Programmable |
Supervision | On EMG inputs, programmable |
Supervision method | Series / parallel resistor |
100 V input | |
Connector | MSTB 2,5 /16-ST |
Amp 1 | 100 V / 70 V / 0 V |
Amp 2 | 100 V / 0 V |
Power handling capacity | 1000 W |
Loudspeaker outputs | 12 x (2 x 6 zones) |
Connectors | MSTB 2,5 /16-ST, floating |
100 V output | 700 W rated per zone |
Volume override types | 3‑wire, 4‑wire (24 V), 4‑wire failsafe |
Output Contacts | |
Connector | MC 1,5/14-ST-3,5 |
Rating | 100 V, 2A, voltage free |
General purpose relays (2x) | NO / COM |
| |
Dimensions (H x W x D) | 88 x 430 x 260 mm (19" wide, 2U high) |
Weight | Approx. 3 kg |
Mounting | Standalone, 19” rack |
Color | Charcoal |
| |
Operating temperature | -10 ºC to +55 ºC (14 ºF to +131 ºF) |
Storage and transport temperature | -40 ºC to +70 ºC (-40 ºF to +158 ºF) |
Relative humidity | <95% |